CJ2M vs CJ3M Comparison Table (CPU Unit Replacement)
This table summarizes the differences in specifications between the OMRON CJ2M CPU unit (CJ2M-CPU□□) and its replacement, the CJ3M CPU unit (CJ3M-CPU□□). Yellow cells are items whose specifications changed from the CJ2M. For the meaning of the symbols, see the legend at the end of the page.
Key specifications
- Program capacity (max.)60k steps→100k steps
- Number of EM banks (max.)4 banks→10 banks
- Number of network variables (tags)2,000→10,000
- BatteryBuilt in→Sold separately
- Battery-free backupNone→Backed up in non-volatile memory
- Built-in capacitor backup time5 minutes→10 days (clock only)
- USB portType-B→Type-C
- Memory cardCF card→SD card
- Built-in EtherNet/IP tag data linksRestrictions such as link size removed; equivalent to the EIP unit
- Built-in EtherNet/IP communication servicesSupports socket services and Modbus server/client
Search
Main Specification Changes in CPU Functions
| Item | CJ2M CJ2M-CPU□□ | CJ3M CJ3M-CPU□□ | Remarks |
|---|---|---|---|
| Max. I/O points | 2,560 points | 5,120 points | |
| Max. number of expansion racks | 3 racks | 7 racks | |
| Max. number of units | 40 units Basic I/O: 40 / Special I/O: 40 CPU Bus: CPU1□ 16, CPU3□ 15 | 80 units Basic I/O: 80 / Special I/O: 80 CPU Bus: CPU1□ 16, CPU3□ 15 | |
| Number of CJ1W-EIP21S/EIP21 units mountable | CPU1□: 2 CPU3□: 2 | CPU1□: 8 CPU3□: 7 | |
| Program capacity | CPU□1: 5k steps CPU□2: 10k steps CPU□3: 20k steps CPU□4: 30k steps CPU□5: 60k steps | CPU□1: 5k steps CPU□2: 10k steps CPU□3: 20k steps CPU□4: 50k steps CPU□5: 100k steps | Increased for □4/□5 only |
| FB program area | 20k steps | 40k steps | |
| Number of EM banks | CPU1□/2□/3□: 1 bank CPU4□/5□: 4 banks | CPU1□/2□/3□: 1 bank CPU4□/5□: 10 banks | |
| Max. FB definitions / max. instances | CPU1□/2□/3□:256/256 CPU4□/5□:2048/2048 | All models 2048 / 2048 | |
| Number of registered network variables (tags) | Max. 2,000 | Max. 10,000 | |
| Data trace memory capacity | 8,000 words | 220,000 words | |
| Battery-free I/O memory backup | No (I/O memory backed up by battery at power OFF) | Yes (backed up in non-volatile memory, no battery needed) | |
| Battery | Built in at shipment (CJ1W-BAT01) | Not built in at shipment Sold separately (CJ1W-BAT01) | Must be mounted to use the clock |
| Clock | Built in (same) | ||
| Built-in capacitor backup time | 5 minutes (without battery) Backs up I/O memory and clock | 10 days (without battery) Backs up clock only | |
| Peripheral USB port | Type-B connector | Type-C connector | |
| Serial port | CPU1□: RS-232C CPU3□: CP1W option board | RS-232C port (all models) | Option board slot removed on CPU3□. RS-422A/485 supported with converter units (CJ1W-CIF11 / NT-AL001) |
| Memory card | HMC-EF□□□ | HMC-SD□□□ (SD memory card) | |
| Power-up time (startup time of the CPU alone) | Approx. 2 s | CPU1□: approx. 2 s CPU3□: approx. 6 s | |
| Current consumption | CPU1□:DC5V 0.5A CPU3□:DC5V 0.7A | CPU1□:DC5V 0.26A、DC24V 0.003A CPU3□:DC5V 0.91A、DC24V 0.003A | 5 V consumption increased on CPU3□. Check the power supply unit capacity |
| Model name returned by Read CPU Unit Data (FINS 0501) | CJ2M-CPU□□ | Returns "CJ2X-CPU□□" | Note that it is not "CJ3M-CPU□□". Shown as CJ3M in CX-One |
Specification Changes in Built-in EtherNet/IP Functions
Comparison of CJ2M-CPU3□ → CJ3M-CPU3□ (built-in EtherNet/IP type).
| Item | CJ2M CJ2M-CPU3□ | CJ3M CJ3M-CPU3□ | Remarks |
|---|---|---|---|
| Number of tag data link connections | 32 | 256 | |
| Packet interval (RPI) | 1 to 10,000 ms (0.5 ms units) | 0.5 to 10,000 ms (0.5 ms units) | |
| Permissible communication bandwidth per unit | 3,000pps | 12,000pps | |
| Number of registrable tags | 32 | 256 | |
| Number of tags per connection | 8 (same) | ||
| Max. link data size per node | 640CH | 184,832CH | |
| Max. data size per connection | 640CH | 722CH | |
| Number of registrable tag sets | 32 | 256 | |
| Max. size of one tag set | 640CH | 722CH | |
| Max. number of tags refreshable per cycle | Output/send: 32 Input/receive: 32 | Output/send: 256 Input/receive: 256 | |
| Data size refreshable per cycle | Output/send: 640 CH Input/receive: 640 CH | Output/send: 6,432 CH Input/receive: 6,432 CH | |
| Explicit messages Class 3 | Number of connections: 128 (same) | ||
| Explicit messages UCMM (unconnected) | Simultaneous communication: max. clients 16 Max. servers 16 | Simultaneous communication: max. clients 32 Max. servers 32 | |
| CIP routing | Supported (same) | ||
| FINS/UDP, FINS/TCP | Supported (FINS/TCP max. 16 connections) (same) | ||
| Socket services | Not possible | Supported (UDP max. 8 sockets, TCP max. 8 sockets) | |
| Modbus server | Not possible | Supported (TCP max. 8 connections, UDP supported) | |
| Modbus client | Not possible | Supported (implemented with FBs using socket services, TCP max. 8 connections / UDP) | |
| EtherNet/IP conformance test | CT17 (A5 compliant in the appendix table) | CT21 | |
| Ethernet interface | 100BASE-TX / 10BASE-T Auto Negotiation / fixed setting | 100BASE-TX / 10BASE-T Auto Negotiation / fixed setting Auto MDI/MDI-X | |
| Carrying over FTP settings | ― | Not carried over | When using FTP, set "Use FTP", the password and the port number again |
| Getting the IP address via BOOTP | "Get from BOOTP server" | Converted to "Get from BOOTP server (once only)" | Same behavior. However, the MAC address changes, so the BOOTP server settings must be changed |
Differences in External Interfaces (Parts)
| Item | CJ2M | CJ3M | Remarks |
|---|---|---|---|
| Battery | Mounted at shipment (CJ1W-BAT01) | Not mounted at shipment (sold separately: CJ1W-BAT01) | |
| DIP switch | Layout and settings are the same | Set to the same ON/OFF states as the CJ2M. SW3/SW4/SW8 on the CJ3M have functions assigned but should be OFF | |
| Status LEDs | RUN、ERR/ALM、INH、PRPHL、COMM、BKUP | RUN、ERR/ALM、INH、COMM、BKUP | The function of each LED is the same. No PRPHL LED |
| Memory card LED | BUSY、MCPWR | SD BUSY、SD PWR | Different name but same function |
| USB port | Type-B | Type-C | |
| Memory card | HMC-EF□□□ | HMC-SD□□□ | |
| RS-232C port (CPU1□) | Connector (D-sub 9-pin) and pin assignment are the same | ||
| Option board slot (CPU3□) | RS-232C and RS-422A/485 option boards (CP1W-CIF□□) can be mounted | No slot → RS-232C port | RS-422A/485 supported with CJ1W-CIF11 (non-isolated) or NT-AL001 (isolated) |
| EtherNet/IP setting switches | Unit number and node address setting (same) | ||
| EtherNet/IP LEDs | 7SEG, MS, NS, COMM, 100M, 10M (same) | ||
| EtherNet/IP port | RJ45 (same) | ||
| Dimensions (H × D × W) | CPU1□: 90×75×31 mm / CPU3□: 90×75×62 mm (same) | ||
| Weight | CPU1□: 130 g max. CPU3□: 190 g max. | CPU1□: 140 g max. CPU3□: 240 g max. | |
Battery, I/O Memory Retention and Clock
| Item | CJ2M | CJ3M | Remarks |
|---|---|---|---|
| Battery mounted at shipment | Mounted | Not mounted | |
| PLC Setup Battery error detection (default) | Detect | Do not detect | Change to "Detect" when using a battery |
| I/O memory | SRAM | Non-volatile RAM | |
| I/O memory retention at power OFF | Backed up by battery | No battery needed | |
| Clock | Built in (same) | ||
| Built-in capacitor backup time for the clock | 5 minutes | 10 days (ambient temperature 40°C) | No battery needed for short power interruptions |
| Battery used | CJ1W-BAT01 (same) | Life 5 years (0 to 55°C) | |
| Clock accuracy (per month) | 55°C: -3.5 to +0.5 min / 25°C: -1.5 to +1.5 min / 0°C: -3 to +1 min (same) | ||
| Setting | CJ2M "Do not detect battery error" | CJ3M "Detect battery error" |
|---|---|---|
| OFF | Detect battery error | Do not detect battery error |
| ON | Do not detect battery error | Detect battery error |
Overview of How to Replace CJ2M with CJ3M
For details on replacement, refer to the Programmable Controller CJ Series Replacement Guide: From CJ2M to CJ3M, catalog number SBCA-150A (as of September 2026), and other materials. This is an excerpted overview.
| Data to migrate | Method A: project file conversion (CJ2M→CJ3M CXP converter) | Method B: simple backup/restore (via memory card) |
|---|---|---|
| Program (including FBs) | ○ | ○ |
| Data types / variable tables | ○ | ○ (variable tables, comments, program index) |
| PLC memory / I/O memory | ○ (PLC memory) | ○ |
| PLC Setup | ○ | ○ |
| I/O table | ○ | ○ |
| Special unit settings | ○ (except built-in EtherNet/IP) | ○ (except built-in EtherNet/IP) |
| Routing tables | Read/transfer separately with CX-Integrator | ○ |
| Built-in EtherNet/IP settings | Not carried over → in the I/O table, "Save Special Unit Parameters" (.xml) for the CJ2M-EIP21, then "Load Special Unit Parameters" for the CJ3M-EIP21S | Not carried over (MS LED flashes red, 7-segment shows "Er" "H8") → migrate following the procedure in the replacement guide |
| Tag data link settings | Upload the entire network with Network Configurator → "Change Device" to CJ3M-CPU3□ → download the entire network (the settings of partner PLCs must also be transferred) | |
| CJ1W-CLK□□ / CJ1W-FLN22 | Read/transfer separately with CX-Integrator (data link tables) / CX-Flnet | |
Restrictions when migrating
- The converter "CJ2M-CJ3MConverter.exe" is available from the Sysmac Studio / CX-One Utility download page. Conversion is not possible if the project contains multiple PLCs (prepare a file with only one CJ2M).
- The converter only changes the model from "CJ2M" to "CJ3M". Change the CPU type (CPU□□) in CX-Programmer after conversion. From models other than CJ2M, migrate by changing the model in CX-Programmer (PLC Setup, I/O table and special unit settings are initialized).
- After conversion, compiling (program check) may produce errors, so check and fix them.
- Simple backup: if the program capacity of the backup is larger than the restore destination, it is not restored.
- Simple backup: if the number of EM banks is smaller at the restore destination, the EM in the file is restored but force-set/reset information is not (e.g. CJ2M-CPU13 → CJ3M-CPU15). If larger, it is not restored (e.g. CJ2M-CPU15 → CJ3M-CPU13).
- Simple backup: if units have been added or special unit numbers differ, it is not restored.
- When using CJ1W-ETN21, if memory all clear is performed, settings cannot be transferred unless the power is cycled or the unit is restarted.
Summary of Points to Note When Replacing
| Item | Description |
|---|---|
| Cycle time | Changing to the CJ3M may change the cycle time. Check the operation of programs that depend on the cycle time. To make it the same as the CJ2M, use the "Minimum cycle time" function in the PLC Setup. |
| Floating-point arithmetic | Real-number calculation results may differ. Check real-type calculation results thoroughly. |
| Battery error detection | The CJ3M defaults to "do not detect". When using the clock, mount a battery and set it to "detect" (note that the meaning of the setting is reversed when migrating). |
| Built-in EtherNet/IP | Neither the model conversion tool nor simple backup carries over the built-in EtherNet/IP settings. FTP settings must be set again. When using BOOTP, change the server side because the MAC address changes. |
| FINS 0501 | The model name is returned as "CJ2X-CPU□□". Action is needed if host applications check it. |
| Power supply capacity | 5 V current consumption of CPU3□ increases from 0.7 A to 0.91 A. Check the power supply unit capacity. |
| Startup time | Power-up of CPU3□ goes from approx. 2 s to approx. 6 s. Pay attention to startup timing with host devices. |
| Memory card | Changed from HMC-EF to HMC-SD. Migrate data by copying it on a PC (files can be used as-is). |
No matching items found.
Legend
| Items whose specifications changed from the CJ2M | |
| (same) | Items with the same specifications on CJ2M and CJ3M (shown with the 2 columns merged) |
| □ | A digit of the model number goes here (e.g. CPU1□ = CPU11 to CPU15, CPU□4 = CPU14 and CPU34) |
| CPU1□ | Built-in RS-232C type |
| CPU3□ | Built-in EtherNet/IP type |
Sources
- OMRON: Programmable Controller CJ Series Replacement Guide: From CJ2M to CJ3M, catalog number SBCA-150A (as of September 2026)
- For details, refer to the CJ3 CPU Unit User's Manual Hardware (SBCA-513), the CJ2/CJ3 CPU Unit User's Manual Software (SBCA-350) and the EtherNet/IP Unit User's Manual (SBCD-342).
- This page is organized based on manufacturer documents. Always check the latest manuals when actually replacing units.
Related pages
OMRON

CJ to NJ Instruction Replacement Guide
A guide to replacing CJ instructions with NJ instructions
PC Tools

KVtoCJ
An application that converts KEYENCE KV series ladder programs into OMRON CJ series ladder programs
PC Tools

CJtoKV
An application that converts OMRON CJ series ladder programs into KEYENCE KV series ladder programs