This table summarizes the differences in specifications between the OMRON NS-V2 programmable terminal (NS□-□□□□-V2) and its replacement, the NS-B series (NB□□W-TW01B-V1-S). Yellow cells are items whose specifications changed from the NS-V2. For the meaning of the symbols, see the legend at the end of the page.

Key specifications

  • BatteryCJ1W-BAT01→Battery-free
  • Power supply primary/secondaryIsolated→Non-isolated (beware of positive grounding)
  • Screen design toolCX-Designer Ver3→CX-Designer Ver4
  • Memory cardCF card→USB memory
  • Resolution (NS12/NS10/NS8)4:3→Wide (1024×600 / 800×480)
  • Panel cutoutSmaller for all sizes→No panel machining with attachment
  • Two-point simultaneous pressPossible→Not possible
  • RS-422A/485Converter adapter→Connect directly to COM2
  • Saving retained memoryAlways→Every 30 s (immediate save with $SB62)
  • Date/time display range1970 to 2106→2024 to 2062
  • Connection to other manufacturers' PLCsPossible→Not possible (only some such as OMRON and Modbus)
  • Repair period7 years after discontinuation→5 years from manufacture date

Search

Recommended replacement models

The following NS-B replacements are recommended according to panel size. Panel cutout dimensions change, so using the matching attachment allows mounting without machining the control panel.

SizeNS-V2
Original
NS-B
Recommended replacement
Matching attachment
15 inchNS15-TX01□-V2NB15W-TW01B-V1-SNB15W-ATT01
12 inchNS12-TS0□□-V2NB10W-TW01B-V1-SNB10W-ATT02
10 inchNS10-TV0□□-V2NB10W-TW01B-V1-SNB10W-ATT02
8 inchNS8-TV0□□-V2NB7W-TW01B-V1-SNB7W-ATT01
5 inchNS5-SQ1□□-V2/NS5-TQ1□□-V2NB5Q-TW01B-V1-SNB5Q-ATT01
Handheld (NSH5)NSH5-SQ□□□-V2No successor
Integrated controller (NSJ)NSJ□-□□□□No successor

* When replacing NS models without V or with V1, first convert the screen data to NS-V2.

General Specifications (All Models)

ItemNS-V2
NS□-□□□□-V2
NS-B
NB□□W-TW01B-V1-S
Remarks
Rated supply voltage24 VDC (same)
Allowable supply voltage range20.4 to 27.6 VDC (same)
Power supply primary/secondaryIsolatedNon-isolatedRisk of short circuit and equipment damage in panels with 24 V side grounding (positive grounding). See the replacement procedure
Power connectionY terminalWire fixed directly to the terminal blockStrip 6.5 mm of insulation, tighten to 0.3 to 0.5 N·m
Grounding methodType D grounding (Class 3 grounding) (same)
Degree of protectionFront operation part IP65 oil-proof, equivalent to NEMA4Front operation part IP65 (dust- and drip-proof from the front only)
Ambient operating temperature0 to 50°C
Restrictions depending on expansion units and mounting angle
0~50℃
Ambient operating humidity35 to 85% RH (0 to 40°C)
35 to 60% RH (40 to 50°C)
No condensation
10 to 90% RH
No condensation
Ambient operating environmentNo corrosive gases (same)
Ambient storage temperature-20 to 60°C (no condensation) (same)
Noise immunityConforms to IEC61000-4-4, 2 kV (power line) (same)
Shock resistance147 m/s², 3 times each in X, Y, Z147 m/s², 3 times each in X, Y, Z
Duration 11 ms or more
Vibration resistance (NS15)5 to 8.4 Hz, 3.5 mm single amplitude
8.4 to 150 Hz, constant acceleration 9.8 m/s²
10 times each in X, Y, Z
10 to 57 Hz, 0.075 mm amplitude
57 to 150 Hz, 9.6 m/s²
30 min each in X, Y, Z
Vibration resistance (NS12/10/8/5)10 to 57 Hz, 0.075 mm amplitude
57 to 150 Hz, constant acceleration 9.8 m/s²
Each in X, Y, Z
10 to 57 Hz, 0.075 mm amplitude
57 to 150 Hz, 9.6 m/s²
30 min each in X, Y, Z
BatteryCJ1W-BAT01 (mounted at shipment)
Life 5 years (25°C)
Replace within 5 days of low battery (LED lit orange)
None (battery-free)NS-B retains the time for 10 days (40°C) after power off
EC DirectivesConforms to EN61131-2 (same)
UL standardsUL508、ANSI/ISA12.12.01UL61010-2-201
UL hazardous locations: no / UL Type-4: no
KC standardsNoneYes
RCM standardsYes (same)
UKCA standardsNoneYes
Marine standardsYes (NK, LR, DNV, RINA, BV, GL, ABS, KR, CR; varies by model)NoneCannot be replaced for marine applications
Screen design toolCX-Designer Ver3CX-Designer Ver4Both versions can be used with CX-One Ver4.70 or later

Specifications by Size (Dimensions and Display)

Compares the differences in dimensions, panel cutout and display for each original size.

15 inch: NS15-TX01□-V2 → NB15W-TW01B-V1-S

ItemNS-V2
NS15-TX01□-V2
NS-B
NB15W-TW01B-V1-S
Remarks
Dimensions (W×H×D)405 × 304 × 75.8 mm356 × 272 × 45.0 mm
Panel cutout (W×H)383.5 × 282.5 mm345.0 × 261.0 mmCan be mounted in the existing cutout with NB15W-ATT01
Panel thickness range1.6 to 4.8 mm (same)
Weight4.2 kg max.2625g
Power consumption45 W max.14W
Display deviceColor high-luminance TFT LCDTFT LCD
Resolution1024 × 768 (same)Conversion offset 0, scale 1
Display colors256 colors (32,768 colors for BMP/JPG parts)16.2M colors
Effective display area304.1 × 228.1 mm304 × 228 mm
Viewing angleLeft/right ±85° / top 70° / bottom 80°Left/right ±89° / top 89° / bottom 89°
Function keys3None
DIP switch6 poles ×1 (for transfer)
6 poles ×1 (for RS-232C/RS-422A switching)
4 poles ×1SW3 and 4 have no function
Reset switch1None
External dimming1 (Lot No. 30114 and earlier only)None
Cable connection directionBottom (same)

12 inch: NS12-TS0□□-V2 → NB10W-TW01B-V1-S

ItemNS-V2
NS12-TS0□□-V2
NS-B
NB10W-TW01B-V1-S
Remarks
Dimensions (W×H×D)315 × 241 × 48.5 mm268.8 × 210.8 × 54.0 mmDepth increases
Panel cutout (W×H)302 × 228 mm258.0 × 200.0 mmCan be mounted in the existing cutout with NB10W-ATT02
Panel thickness range1.6 to 4.8 mm (same)
Weight2.5 kg max.1465g
Power consumption25 W max.8W
Display deviceColor high-luminance TFT LCDTFT LCD
Resolution800 × 6001024 × 600Conversion X coordinate +112, scale 1
Display colors256 colors (32,768 colors for BMP/JPG parts)65,536 colors
Effective display area246.0 × 184.5 mm211 × 133 mmDisplay area becomes smaller
Viewing angleLeft/right ±60° / top 45° / bottom 75°Left/right ±80° / top 75° / bottom 80°
DIP switch6 poles ×1 (for transfer)4 poles ×1SW3 and 4 have no function
Cable connection directionBottomRear (different direction)If there is no rear space, use a side-exit connector

10 inch: NS10-TV0□□-V2 → NB10W-TW01B-V1-S

ItemNS-V2
NS10-TV0□□-V2
NS-B
NB10W-TW01B-V1-S
Remarks
Dimensions (W×H×D)315 × 241 × 48.5 mm268.8 × 210.8 × 54.0 mm
Panel cutout (W×H)302 × 228 mm258.0 × 200.0 mmCan be mounted in the existing cutout with NB10W-ATT02
Weight2.5 kg max.1465g
Power consumption25 W max.8W
Resolution640 × 4801024 × 600Conversion X coordinate +112, scale 1.25. The NS10 comparison table in the guide states "1024×768"
Display colors256 colors (32,768 colors for BMP/JPG parts)65,536 colors
Effective display area215.2 × 162.4 mm211 × 133 mm
Viewing angleLeft/right ±60° / top 35° / bottom 65°Left/right ±80° / top 75° / bottom 80°
DIP switch6 poles ×1 (for transfer)4 poles ×1SW3 and 4 have no function

8 inch: NS8-TV0□□-V2 → NB7W-TW01B-V1-S

ItemNS-V2
NS8-TV0□□-V2
NS-B
NB7W-TW01B-V1-S
Remarks
Dimensions (W×H×D)232 × 177 × 48.5 mm202.0 × 148.0 × 46.0 mm
Panel cutout (W×H)220.5 × 165.5 mm191.0 × 137.0 mmCan be mounted in the existing cutout with NB7W-ATT01
Panel thickness range1.6 to 4.8 mm (same)
Weight2.0 kg max.705g
Power consumption25 W max.7W
Display deviceColor high-luminance TFT LCDTFT LCD
Resolution640 × 480800 × 480Conversion X coordinate +80, scale 1
Display colors256 colors (32,768 colors for BMP/JPG parts)65,536 colors
Effective display area170.9 × 128.2 mm154 × 85 mmDisplay area becomes smaller because it is 7-inch wide
Viewing angleLeft/right ±65° / top 50° / bottom 60°Left/right ±80° / top 60° / bottom 80°
DIP switch6 poles ×1 (for transfer)2 poles ×1
Reset switch1 (same)
Cable connection directionBottomRear (different direction)Side-exit hood: XM2S-0921 (OMRON)

5 inch: NS5-□Q1□□-V2 → NB5Q-TW01B-V1-S

ItemNS-V2
NS5-□Q1□□-V2
NS-B
NB5Q-TW01B-V1-S
Remarks
Dimensions (W×H×D)195 × 142 × 54 mm184.0 × 142.0 × 46.0 mm
Panel cutout (W×H)184 × 131 mm172.4 × 131.0 mmCan be mounted in the existing cutout with NB5Q-ATT01
Panel thickness range1.6 to 4.8 mm (same)
Weight1.0 kg max.660g
Power consumption15 W max.7W
Display deviceColor high-luminance TFT LCDTFT LCD
Resolution320 × 240 (same)Conversion offset 0, scale 1
Display colors256 colors (32,768 colors for BMP/JPG parts)65,536 colors
Effective display area117.2 × 88.4 mm113 × 85 mm
Viewing angleLeft/right ±70° / top 70° / bottom 50°Left/right ±80° / top 70° / bottom 70°
DIP switch6 poles ×1 (for transfer)2 poles ×1
Reset switch1 (same)
Cable connection directionBottomRear (different direction)Side-exit hood: XM2S-0921 (OMRON)

Performance Specifications (All Models)

ItemNS-V2NS-BRemarks
Backlight life50,000 hours min.50,000 hours min.
(room temperature 25°C, brightness 40%)
Conditions now stated
Brightness adjustment32 levels by touch panel operation (same)
Front LED lit greenNormal operationFirst startup / startup after screen data download / calibration mode
Front LED flashing greenMemory card transfer completed normallyNot supportedNS-B notifies transfer status with a buzzer
Front LED lit orangeBacklight error detected right after power ONNot supported
Front LED flashing orangeChecking file system right after power ONNot supported
Front LED lit redNormal operation with low or no batteryNot supported
Front LED flashing redMemory card transfer in progressNot supported
Rear LED (MC PWR)Lit green: memory card powered
Off: power stopped
None
Touch switch methodMatrix resistive filmAnalog resistive filmTouch position may drift over time. Calibrate periodically
Two-point simultaneous pressPossibleNot possible
Touch switch life1 million operations min. (same)
Entering the System MenuPress 2 of the 4 screen corners simultaneouslyDouble-tap 1 of the 4 screen corners

External Interfaces

ItemNS-V2NS-BRemarks
Memory card1 slot (CompactFlash)
HMC-EF183 / EF283 / EF583
No slot (use USB memory)
FZ-MEM16G
No compatibility with data used on NS-V2
SD cardNone1 port on NB15 only (support coming soon)
USB Type-A (host)1 port (same)
USB Type-B (slave)1 port (same)
RS-232C1 port on NS15 only, 2 ports on others2 ports (COM1, COM2)
RS-422A/4851 port on NS15 only (switched by DIP)
Others use an RS-422A converter adapter (NS-AL002)
COM2 can be used as RS-422A/485Select the communication standard in the communication settings of CX-Designer V4
Ethernet1 port on Ethernet-equipped models only1 port (all models)
Controller LinkOption board (NS-CLK21)None
Video output1 portNone
Video inputOption board (NS-CA001 / CA002)None
+5 V supply on serial port BYes (pin 6)NoneBarcode readers need an external 5 V supply
Screen transfer over serial connectionPossibleNot possibleTransfer via USB / Ethernet / USB memory

Pin assignment of serial port B (COM2)

PinNS-V2
RS-232C
NS-B
RS-232C / RS-485 / RS-422A
Remarks
1―SDB+: — / — / send data (+)
2SD (send data) (same)
3RD (receive data) (same)
4RS (request to send)RS (not used)NS-B does not support RS/CS functions
5CS (clear to send)CS (not used)NS-B does not support RS/CS functions
6+5VRDB+: — / RS485B send/receive data (+) / receive data (+)
7―SDA-: — / — / send data (-)
8―RDA-: — / RS485A send/receive data (-) / receive data (-)
9SG (signal ground) (same)

Change in RS-422A/485 connection: NS-V2 was connected with loose wires to the terminal block (RDA-, RDB+, SDA-, SDB+, FG) of the RS-232C/RS-422A converter unit, but NS-B connects directly to the D-sub 9-pin COM2. Refit the connector according to the signals in the table above, set the communication standard to "RS-422A" (or "RS-485") in [Communication Settings] in CX-Designer V4 and transfer. The PLC connection cable NB-RSEXT-2M (RS-422A/485, 2 m) can also be used.

Barcode reader: For the V410-HDS4608SR, supply 5 V with the AC adapter V410-AC0-1 and use the connection cable V430-WPLC-2M.

Connectable Devices

Connection targetNS-V2NS-BRemarks
Serial: SYSMAC PLC (CJ2/CS/CJ/CV/C)Possible (same)NT Link (1:N), NT Link (1:1), Host Link
Serial: MELSEC-APossibleNot possible
Serial: MELSEC-FPossibleNot possible
Serial: MELSEC-A (PrgCon)PossibleNot possible
Serial: MELSEC-Q (PrgCon)PossibleNot possible
Serial: MELSEC-Q/QnAPossibleNot possible
Serial: SIMATIC S7-300PossibleNot possible
Serial: temperature controllerPossible (same)
Serial: Memory LinkPossible (same)
Serial: barcode readerPossible (same)COM2 needs an external 5 V supply
Serial: modemPossibleNot possible
Serial: YASKAWA MPPossibleNot possible
Serial: Varispeed / VS miniPossibleNot possible
Serial: Modbus (Modicon Address Style)Possible (same)
Serial: Modbus (IEC61131 Address Style)Possible (same)
Serial: SLC500 / MicroLogixPossibleNot possible
Serial: PLC-5PossibleNot possible
Serial: ControlLogix / CompactLogixPossibleNot possible
Serial: Yokogawa (FA-M3)PossibleNot possible
Ethernet:SYSMAC CV/CS1/CJ1/CP1Possible (same)FINS、EtherNet/IP
Ethernet:SYSMAC CJ2Possible (same)
Ethernet:SYSMAC NJ/NXPossible (same)
Ethernet:TrajexiaPossibleNot possible
Ethernet:Modbus TCPPossibleNot possible
Controller LinkPossibleNot possible
PrinterPossibleNot possiblePrinter printing function removed

Options

ProductFor NS-V2For NS-BRemarks
Anti-reflection sheet 15 inchNS15-KBA04NB15W-KBA04Must be replaced
Anti-reflection sheet 12/10 inchNS12-KBA04NB10W-KBA04Must be replaced
Anti-reflection sheet 8→7 inchNS7-KBA04NB7W-KBA04Must be replaced
Anti-reflection sheet 5 inchNT30-KBA04NB5Q-KBA04Must be replaced
Attachment―NB15W-ATT01 (15 inch)
NB10W-ATT02 (12/10 inch)
NB7W-ATT01 (7 inch)
NB5Q-ATT01 (5 inch)
Mounts in the existing panel cutout
Memory cardHMC-EF183/EF283/EF583(CF)FZ-MEM16G (USB memory)Must be replaced
Barcode readerV520-RH21-6 (same)
PT-PLC connection cable RS-232CXW2Z-200T (2 m) / XW2Z-500T (5 m) (same)For CP/CJ/CS series
PLC connection cable RS-422A/485NB-RSEXT-2M (2 m) (same)
Video input unitNS-CA001/NS-CA002Cannot be used
Controller Link I/F unitNS-CLK21Cannot be used
BatteryCJ1W-BAT01Not neededBattery-free
RS-422A converter adapterNS-AL002/CJ1W-CIF11Not neededCOM2 supports RS-422A/485

Differences in DIP Switches (Memory Card Transfer)

ItemNS-V2
6 poles
NS-B
SW1, SW2
Remarks
Bank specificationSW1 to 4: specify banks 1 to 4Only bank 1 can be specified by DIPBanks 2 to 4 are used in manual transfer mode
Automatic downloadSW5 OFF, SW6 OFF + bank specificationSW1 ON、SW2 ONAutomatic download from external memory at startup
Automatic uploadSW5 ON, SW6 OFF + bank specificationSW1 OFF、SW2 ON
Manual transferSW6 ONSW1 ON、SW2 OFFStarts the memory card transfer function at startup
Normal operationAll OFFSW1 OFF, SW2 OFF (user project mode)
RS-232C/RS-422A switchingSwitched by DIP on NS15 onlySwitched in CX-Designer communication settings
Transfer status notificationLED (flashing orange: transferring / flashing green: complete / flashing red: error)Buzzer (short every 1 s: transferring / short every 3 s: complete / long every 3 s: error)

Software Changes

ItemNS-V2NS-BRemarks
Retained memory save timingAlways savedSaved every 30 sApplies to: user alarm history, data logs, operation logs, internal holding bits/words ($SB, $SW). For immediate save set $SB62 to 1 (returns to 0 when complete)
Date/time display range (lower limit)1970-01-01 00:00:002024-01-01 00:00:00
Date/time display range (upper limit)2106-02-07 06:28:152062-01-09 03:14:07
Time retentionBacked up by battery (initialized at power off if not mounted)10 days after power off (40°C)To synchronize with the PLC, use the SAP [PLC→NS time adjustment]
Object colorsColor number specification is the same (same)Appearance differs due to LCD differences (e.g. color No. 5 purple R128 G0 B128)
CX-DesignerVer3 ([CX-Designer] folder)Ver4 ([CX-DesignerV4] folder)Opening an IPP file automatically launches the appropriate version
Printer printingYesRemoved
Video display / video captureYesRemoved
Ladder monitorYesSupport coming soon
PLC data traceYesSupport coming soon
Device monitorYesSupport coming soon
Memory card transfer toolYesSupport coming soon
Programming console function (C/CS series)YesRemoved (support planned in the future)
NJ troubleshooterYesRemoved (support planned in the future)
Switch boxYesRemoved (support planned in the future)
SPMAYesRemoved (support planned in the future)
Command button: show system menu (switch box)YesRemoved (support planned in the future)Same for multifunction
Command button: video control (video capture / image adjustment / vision sensor console output)YesRemovedSame for multifunction
Multifunction: show system menu (ladder monitor / PLC data trace)YesRemoved (support coming soon)
Multifunction: show system menu (programming console C/CS, troubleshooter NJ)YesRemoved (support planned in the future)

Changes in System Memory ($SB/$SW)

AddressNS-V2NS-BRemarks
$SB4Battery low notificationReservedRemoved because battery-free
$SB15Video display controlReservedVideo functions not supported
$SB20Contrast adjustment (+10 levels)ReservedFunction removed
$SB21Contrast adjustment (+1 level)ReservedFunction removed
$SB22Contrast adjustment (-1 level)ReservedFunction removed
$SB23Contrast adjustment (-10 levels)ReservedFunction removed
$SB24Execute video captureReservedVideo functions not supported
$SB25Start screen printing / screen captureStart screen capturePrinter functions not supported
$SB26Stop screen printingReservedPrinter functions not supported
$SB27Print printer test patternReservedPrinter functions not supported
$SB28Printer head cleaningReservedPrinter functions not supported
$SB29Start printer status checkReservedPrinter functions not supported
$SB30Printer operating status / screen capture in progressScreen capture in progressPrinter functions not supported
$SB31Printer status / screen capture resultScreen capture resultPrinter functions not supported
$SB48Memory card remaining capacity warning flagUSB memory remaining capacity warning flag
$SB49Execute memory card power OFFExecute USB memory removal
$SB50Memory card removable status (power cut)USB memory removable status
$SB62ReservedSave internal holding memoryAdded a function to explicitly save retained memory
$SW11Switch screen printing / screen captureReservedPrinter functions not supported
NT-compatible PT status control area 3ch bit7Switch screen printing / screen captureStart screen capturePrinter functions not supported
NT-compatible PT status notification 1ch bit7Printer operating status / screen capture in progressReservedPrinter functions not supported
NT-compatible PT status notification 1ch bit13Battery low notificationReservedRemoved because battery-free

Screen Data Conversion Rules

When converting NS-V2 screen data (.IPP) for NS-B with [Tools] - [Convert] - [Import] in CX-Designer V4, the display positions and sizes of parts are converted according to the following rules based on the resolution difference (the Y coordinate is not offset).

Model before conversionModel after conversionX coordinate offsetPart size scale
NS15-TX0□-V2NB15W-TW01B-V1-S01
NS12-TS0□ (no suffix / -V1 / -V2)NB10W-TW01B-V1-S1121
NS10-TV0□ (no suffix / -V1 / -V2)NB10W-TW01B-V1-S1121.25
NS8-TV0□-V1/TV1□-V1/TV0□-V2、NS7-SV0□NB7W-TW01B-V1-S801
NS5-SQ0□-V1 / SQ0□, SQ1□, TQ0□, TQ1□, MQ0□, MQ1□-V2NB5Q-TW01B-V1-S01
NSJ□、NSH5、NSA12-TX01B、NS-RuntimeCannot be converted (convert the model to V2 first)

Before converting, set the PC display scaling to 100% (the scaling affects CX-Designer font sizes). Parts placed outside the screen on the NS-V2 may become visible due to the resolution difference.

Warranty and Repair Period

ItemNS SeriesNS-B seriesRemarks
Warranty period1 year from the date of sale by OMRON (same)
Repair periodRepairs and analysis accepted for 7 years after discontinuationRepairs and analysis accepted for 5 years from the manufacture date (5 years after discontinuation)
Repair method―Handled by replacement with a new product
Analysis only identifies the faulty part at the module level

Overview of the NS-V2 → NS-B Replacement Procedure

Caution: always check the existing equipment for positive grounding (24 V side grounding)

The internal power supply of the NS-B is non-isolated. If the +24 V side and ground side of the NS-B are short-circuited (24 V side grounding), +24 V and power GND are shorted via the signal GND/FG of a connected PC or similar, leading to equipment damage. Check both the wiring diagrams and the actual equipment with a tester or similar.

If they are short-circuited, either Measure 1: change the wiring so the 24 V side is not grounded, or Measure 2: insert an isolated DC power supply between the external power supply and the NS-B for isolation.

  1. Preparation: check for positive grounding → upload screen data from the NS-V2 (CX-Designer Ver3, USB) → convert for NS-B in CX-Designer V4, check and fix places affected by function changes
  2. Removing the NS-V2: power OFF → remove all cables → remove the memory card (if used) → remove from the operation panel
  3. Mounting the NS-B: mount the attachment → mount the NS-B → wire the cables (cut off the Y terminals and connect power directly to the terminal block; rework RS-422A/485 to D-sub 9-pin) → insert USB memory (if used)
  4. Startup: power ON → download screen data (CX-Designer V4, USB) → check written values, screen transitions and displayed values on the actual equipment → start operation

If CX-Designer is not available on site, you can turn ON DIP SW1 and SW5 on the NS-V2 to automatically upload to the memory card (BANK1) and read it on a PC. For the NS-B, write it to USB memory and start with DIP SW1 and SW2 ON to download automatically (return SW1 and SW2 to OFF afterwards).

Summary of Points to Note When Replacing

ItemDescription
Positive groundingThe NS-B power supply is non-isolated. In panels with 24 V side grounding, +24 V and power GND can short via the FG of a PC etc., damaging equipment. Always check with wiring diagrams and a tester, and either wire so the 24 V side is not grounded or insert an isolated DC power supply.
Connectable DevicesSerial connections to Mitsubishi, Siemens, Rockwell, Yokogawa, Yaskawa and others, Modbus TCP, Trajexia, Controller Link and printers cannot be connected. OMRON SYSMAC (serial / FINS / EtherNet/IP), Modbus (serial), temperature controllers, Memory Link and barcode readers can.
Supported standardsDoes not support marine standards, UL hazardous locations or UL Type-4. The UL standard changes to UL61010-2-201.
Panel cutoutThe panel cutout becomes smaller for all sizes. The matching attachment (NB□□-ATT0□) allows mounting without panel machining. Depth of the NB10W increases from 48.5 mm to 54.0 mm.
Cable connection directionPort direction changes on models other than NB15. If there is no rear space, use a D-sub side-exit hood (XM2S-0921 / MAH90-9-M2.6) or a commercially available side-exit connector.
Power wiringY terminals cannot be used. Cut off the Y terminal, strip 6.5 mm of insulation and fix the wire directly to the terminal block (0.3 to 0.5 N·m).
RS-422A/485No converter adapter needed. Wire directly to the D-sub 9-pin COM2 and select the communication standard in the CX-Designer V4 communication settings.
Barcode readerCOM2 does not supply 5 V. Supply 5 V with an external power supply (such as V410-AC0-1) and connect with V430-WPLC-2M.
Screen dataConvert with CX-Designer V4. NS12/NS10/NS8 get a wide resolution and part positions are offset in the X direction (NS10 is scaled 1.25×). Parts placed outside the screen may become visible.
Touch operationTwo-point simultaneous press is not possible. Open the system menu by double-tapping one of the 4 corners. Calibrate periodically because it uses analog resistive film.
Retained memoryBecause saving happens every 30 s, changes made just before a power cut may not be retained. For immediate save, turn $SB62 ON.
Date and timeThe display range is 2024-01-01 to 2062-01-09. Being battery-free, time is retained for about 10 days (40°C). To synchronize with the PLC, use the SAP [PLC→NS time adjustment].
System memory$SB/$SW related to battery, video, contrast and printer are changed to reserved. Screens and PLC programs referencing them must be fixed.
Repair periodNS-B: 5 years from manufacture date (5 years after discontinuation). Repairs are handled by replacement with a new product.
For the procedure for migrating programs and screen data, refer to OMRON's "Replacement Guide: From NS-V2 to NS-B (SBSA-099A)".

No matching items found.

Legend

Items whose specifications changed from the NS-V2
(same)Items with the same specifications on NS-V2 and NS-B (shown with the 2 columns merged)
□Alphanumeric characters of the model number go here (e.g. NS8-TV0□□-V2 = NS8-TV00-V2, NS8-TV01B-V2, etc.)
Not possible / cannot be usedItems that cannot be connected or used on NS-B (red text)
NB□□WNS-B series body (NB15W / NB10W / NB7W; NB5Q for 5 inch)

Sources

  • OMRON: Programmable Terminal NS-B Series Replacement Guide: From NS-V2 to NS-B, catalog number SBSA-099A (as of September 2026)
  • For details, refer to the NS-B Series User's Manual Hardware (SBSA-562), Software (SBSA-563), Host Connection (SBSA-564) and the CX-Designer Version 4 Operation Manual (SBSA-566).
  • This page is organized based on manufacturer documents. Always check the latest manuals when actually replacing units.

Related pages

OMRON

CJ2M vs CJ3M comparison table

Differences Between CJ2M and CJ3M

Specification comparison table for replacing the CJ2M CPU unit with its successor, the CJ3M

OMRON

CJ to NJ Instruction Replacement Guide

CJ to NJ Instruction Replacement Guide

A guide to replacing CJ instructions with NJ instructions

Comments