How to Connect an IAI SCON

Overview

A set of function blocks for commanding servo ON, homing, JOG and positioning of an IAI SCON position controller from a PLC
In this sample, the PLC and SCON are connected via EtherNet/IP
The SCON operating mode is set to "Full direct value mode" (32 bytes)

SCON hardware configuration
EtherNet/IP connection configuration of the PLC and IAI SCON

NOTE

This sample uses an SCON, but it should also work with other controllers such as the PCON
It should also work in other operating modes such as "Half direct value mode" by changing the structure
When connecting via EtherCAT, MOVE the values of the variables set in the I/O map into the structure

Function block list

  • Enable operation (SconPower)
  • Homing (SconHome)
  • Jog operation (SconMoveJog)
  • Move (SconMove)

Symbols

Enable operation (SconPower)

Ready to run
In-out
AxisStatus
Axis input
AxisCmd
Axis output
Output
Status
Ready to run

Homing (SconHome)

Homing
In-out
AxisStatus
Axis input
AxisCmd
Axis output

Jog operation (SconMoveJog)

Jog operation
In-out
AxisStatus
Axis input
AxisCmd
Axis output
Output
PositiveEnable
JOG+
NegativeEnable
JOG-

Move (SconMove)

Move
In-out
AxisStatus
Axis input
AxisCmd
Axis output
Input
position
Target position
PosBand
Positioning width
Speed
Speed
ZonePositive
Zone boundary +
ZoneNegative
Zone boundary -
Acceleration
Acceleration
Deceleration
Deceleration
CurrentLimit
Pressing current limit
CurrentThreshold
Load current threshold
PUSH
Pressing specification
DIR
Pressing direction FALSE=positioning TRUE=pressing
Output
PEND
Positioning complete signal
PSFL
Pressing missed

Structures

Input structure
Input structure

Output structure
Output structure

EtherNet/IP tag data link settings

Network Configurator tag data link
Network Configurator tag data link

Download