Command list
Command
I/O Memory Area Read (01 01)
Reads data from a consecutive memory area
The maximum read size is 999 words over Ethernet
It may be smaller depending on the networks the command passes through
Example: command reading 10 words from DM100
Response format
| MRC | SRC | MRES | SRES | TEXT |
| Command code | End code | Read data |
| 01 | 01 | | | |
Example: response after reading 10 words from DM100
| 01 | 01 | 00 | 00 | 00 01 00 02 00 03...00 0A |
* The read data is 20 bytes
I/O Memory Area Write (01 02)
Writes data to a consecutive memory area
The maximum write size is 997 words over Ethernet
It may be smaller depending on the networks the command passes through
Example: command writing 2 words, 0001 to DM100 and 0002 to DM0101
| 01 |
02 |
82 |
00 |
64 |
00 |
00 |
02 |
00 01 00 02 |
* The write data is 4 bytes
Response format
| MRC | SRC | MRES | SRES |
| Command code | End code |
| 01 | 02 | | |
Example: normal completion response
I/O Memory Area Fill (01 03)
Writes the same value to a consecutive memory area
Example: command writing 0000 to 10 words from DM100
| MRC | SRC | TEXT |
| 01 |
03 |
82 |
00 |
64 |
00 |
00 |
0A |
00 |
00 |
Response format
| MRC | SRC | MRES | SRES |
| Command code | End code |
| 01 |
03 |
|
|
Example: normal completion response
Multiple I/O Memory Area Read (01 04)
Command format
Example: command reading the values of DM100, DM200 and W10
| 01 |
04 |
82 |
00 |
64 |
00 |
00 |
82 |
00 |
C8 |
00 |
00 |
B1 |
00 |
0A |
00 |
Response format
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
Memory type |
Read data |
Memory type |
Read data |
Memory type |
Read data |
| 01 |
04 |
|
|
|
|
|
|
|
|
|
|
|
Example: response after reading the values of DM100, DM200 and W10
| 01 |
04 |
00 |
00 |
82 |
12 |
34 |
82 |
02 |
00 |
B1 |
12 |
34 |
Change Operating Mode (RUN) (04 01)
Command format
| MRC | SRC | TEXT |
| Command code |
Program number |
Mode |
| 04 |
01 |
FF |
FF |
|
Mode: 02 = MONITOR mode, 04 = RUN mode
Example: command changing to MONITOR mode
Response format
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 04 |
01 |
|
|
Example: normal completion response
Change Operating Mode (STOP) (04 02)
Command format
| MRC | SRC | TEXT |
| Command code |
Program number |
| 04 |
02 |
FF |
FF |
Example: stop command
Response format
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 04 |
01 |
|
|
Example: normal completion response
CPU Unit Data Read (05 01)
Command format
| MRC | SRC | TEXT |
| Command code |
Data to read |
| 05 |
01 |
|
* The data to read is 00 or 01
Response format
When the data to read is 00
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
CPU unit model |
System version |
System information |
Area information |
| 05 |
01 |
|
|
20byte |
20byte |
40byte |
12byte |
When the data to read is 01
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
CPU Bus Unit configuration |
Remote I/O information |
CPU unit information |
| 05 |
01 |
|
|
64byte |
|
|
CPU Unit Status Read (06 01)
Command format
| MRC | SRC |
| Command code |
| 06 |
01 |
Response format
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
Operating status |
Operating mode |
| 06 |
01 |
|
|
|
|
|
|
|
TEXT (continued) |
|
Fatal error information |
Message present |
Error code |
Error message |
|
|
|
|
|
|
|
16byte |
Cycle Time Read (06 20)
Command format
| MRC | SRC | TEXT |
| Command code |
Parameters |
| 06 |
20 |
|
* The parameter is 00 or 01
Response format
When the parameter is 00 (initialize)
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 06 |
20 |
|
|
When the parameter is 01 (read)
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
Average cycle time |
Maximum cycle time |
Minimum cycle time |
| 06 |
20 |
00 |
00 |
4byte |
4byte |
4byte |
Clock Read (07 01)
Command format
| MRC | SRC |
| Command code |
| 07 |
01 |
Response format
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
Year |
Month |
Day |
Hour |
Minute |
Second |
Day of week |
| 07 |
01 |
|
|
|
|
|
|
|
|
|
* Day of week: 00 = Sunday to 06 = Saturday
Clock Write (07 02)
Command format
| MRC | SRC | TEXT |
| Command code |
Year |
Month |
Day |
Hour |
Minute |
Second |
Day of week |
| 07 |
02 |
|
|
|
|
|
|
|
* The parameter is 00 or 01
Response format
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 07 |
02 |
|
|
Error Clear (21 01)
Command format
| MRC | SRC | TEXT |
| Command code |
Error code to clear |
| 21 |
01 |
|
|
Response format
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 21 |
01 |
|
|
Error Log Read (21 02)
Command format
| MRC | SRC | TEXT |
| Command code |
Start record No. |
Number of records to read |
| 21 |
02 |
|
|
|
|
Response format
| MRC | SRC | MRES | SRES | TEXT |
| Command code |
End code |
Maximum number of records |
Number of stored records |
Number of records read |
| 21 |
02 |
|
|
|
|
|
|
|
|
|
TEXT (continued) |
|
Error log data |
|
Error log data |
|
10byte |
|
10byte |
Error Log Clear (21 03)
Command format
| MRC | SRC |
| Command code |
| 21 |
03 |
Response format
| MRC | SRC | MRES | SRES |
| Command code |
End code |
| 21 |
03 |
|
|
How to Specify Memory Types and Addresses
Configuration
The memory type and address are specified together in 4 bytes
| Memory type | Address |
| Word | Bit |
|   |
|
|
|
Memory type
The memory type and address are specified together in 4 bytes
| Area type |
Data type |
Memory type |
Command availability |
| 0101 |
0102 |
0103 |
0104 |
| Bit |
CIO |
30 |
○ |
○ |
x |
○ |
| WR |
31 |
| HR |
32 |
| AR |
33 |
| DM |
02 |
| E0-EF |
20-2F |
| E10-E18 |
E0-E8 |
| EM current bank |
0A |
| Task flags |
06 |
| Clock pulses |
07 |
| Condition flag |
07 |
| Bits with forced ON/OFF status |
CIO |
70 |
x |
x |
x |
○ |
| WR |
71 |
| HR |
72 |
| Word |
CIO |
B0 |
○ |
○ |
○ |
○ |
| WR |
B1 |
| HR |
B2 |
| AR |
B3 |
| DM |
82 |
| E0-EF |
A0-AF |
| E10-E18 |
60-68 |
| EM current bank |
98 |
| Words with forced ON/OFF status |
CIO |
F0 |
x |
x |
x |
○ |
| WR |
F1 |
| HR |
F2 |
| Up flags |
TIM |
09 |
x |
x |
x |
○ |
| CNT |
| Up flags with forced ON/OFF status |
TIM |
49 |
x |
x |
x |
○ |
| CNT |
| Current value |
TIM |
89 |
○ |
○ |
○ |
○ |
| CNT |
| Index register IR |
DC |
x |
| Data register DR |
BC |
Address
For the address, the first 2 bytes are the address and the next byte specifies the bit position
Example: to specify DM100
For the address, the first 2 bytes are the address and the next byte specifies the bit position
| Memory type | Word | Bit position |
| 82 |
00 |
64 |
00 |
Example: to specify CIO256.14
For the address, the first 2 bytes are the address and the next byte specifies the bit position
| Memory type | Word | Bit position |
| 30 |
01 |
00 |
0E |
Structure of Read and Write Data
The format of read data and write data differs depending on whether bits, bits with forced ON/OFF status, words, or words with forced ON/OFF status are specified
== When bits are specified ==
One bit is represented by one byte
|   |
|
0x00 = OFF、0x01 = ON |
Example: representing the 3 bits OFF-ON-OFF
== When bits with forced ON/OFF status are specified ==
One bit is represented by one byte
|   |
|
|
|
|
|
Bit 0: 0 = OFF, 1 = ON |
|
Bit 1: 0 = not forced, 1 = forced |
Example: representing forced OFF
Example: representing forced ON
== When words are specified ==
One word is represented by 2 bytes
== When words with forced ON/OFF status are specified ==
One word is represented by 4 bytes
|   |
|
|
|
|
|
| 15-8 |
7-0 |
15-8 |
7-0 |
|
Bit |
| Forced status |
Current value |
|
|