What Are FINS Commands?

FINS commands are the command system of OMRON's common network message service
By sending FINS commands to OMRON devices connected via Ethernet, Controller Link, Host Link and so on, you can receive the responses to the commands
Commands can also be sent to Special Units, not only CPU units
Using the network relay function, you can access across up to three network levels


This explains how to send FINS commands from a PC to a CPU unit via Ethernet
Example configuration for sending FINS commands from a PC to an OMRON PLC

Manuals

For an explanation of FINS commands,
see the Communications Commands Reference Manual

For how to send over FINS-UDP and FINS-TCP,
see "Section 7 Creating Host Applications for FINS Communications" in the Ethernet Unit Operation Manual (Construction of Applications)

FINS frame

FINS command frame
FINS headerFINS command
ICFRSVGCT DNA DA1 DA2 SNA SA1 SA2 SID MRCSRCTEXT
(Example) 800002000100000A0001
FINS response frame
FINS headerFINS command
ICFRSVGCTDNADA1DA2 SNASA1SA2SIDMRCSRCMRESSRESTEXT
(Example) C00002000A0000010001

Parts of the FINS header that need to be changed

FINS header
ICF0x80 when sending
RSVFixed 0x00
GCTFixed 0x02
Destination
FINS
address
DNADestination network address (0x00 for the local network)
DA1Destination node address
DA2Destination unit address (to the CPU = 0x00)
Source
FINS
address
SNASource network address (0x00 for the local network)
SA1Source node address (any value 01-FE that does not clash with the destination seems fine)
SA2Source unit address (fixed 0x00)
SIDAny service ID (usually a value incremented for each communication)

FINS address

A FINS address consists of 3 bytes with the following meanings

FINS address
1st byte2nd byte3rd byte
Network addressNode addressUnit address

FINS address details

FINS command

Typical commands
Command
MRC SRC
DescriptionOperands
0101Memory readAddress, number of elements
0102Memory writeAddress, number of elements, write data
0103FillAddress, number of elements, write data
0104Multiple readMultiple read addresses
0401Start operationMONITOR or RUN
0402Stop operation
0501CPU unit information
0601Read CPU status
0620Cycle timeInitialize or read
0701Clock read
0702Clock write
2101Error clearError code
2102Error historyStart record No., number of records
2103Error log clear

How to specify memory types and addresses


FINS-UDP and FINS-TCP

Comparison

  • FINS-UDP

  • FINS-TCP

  • - Connectionless, so there is no limit on the number of connections

    - Broadcast can be used

    - Less reliable than TCP
    Reliability drops when communicating across multi-level IP networks (e.g. the internet)

    - Fast
    No connection procedure, so the time it takes is saved

  • - Limited number of connections

    - Broadcast cannot be used

    - Highly reliable
    Reliable even across multi-level IP networks (e.g. the internet)

    - Slower than UDP
    The connection procedure makes processing take longer than UDP/IP

    - Connections can be restricted
    The clients that can connect can be restricted in the server settings

  • Frame structure
    Ethernet2 IP UDP FINS FCS

  • Frame structure
    Ethernet2 IP TCP FINS-TCP
    header
    FINS FCS

Comparison of FINS-UDP and FINS-TCP

Related pages

TCP and UDP communication test tool

Analyze and test TCP and UDP communication

ComCom

An application that sends messages you create using Ethernet socket communication

FINS communication test tool

Analyze and test FINS communication

FinsMes

An application that sends FINS messages using Ethernet socket communication

Python FINS communication

OMRON FINS Communication

FINS communication with OMRON products

FAQ

What are FINS commands?

FINS commands are the command system of OMRON's common network message service. They let you access PLCs and Special Units via Ethernet, Controller Link and other networks.

What is a FINS address?

A FINS address is a 3-byte destination identifier made up of a network address, a node address and a unit address.

What is the difference between FINS-UDP and FINS-TCP?

FINS-UDP is connectionless and fast but less reliable than TCP; FINS-TCP is connection-oriented and more reliable.

What are typical FINS commands?

Memory read (0101), memory write (0102), CPU status read (0601), clock read (0701) and so on.